Zeta Alarm Systems Infinite 8 Manual de Instalação Página 18

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 36
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 17
INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624
Approved Document No: GLT-211-7-1
Issue 1.0 Author: MG Date: 22/1/2013 PAGE 17
11 OTHER CONNECTIONS
11.1 Repeater connection
The Infinity ID2 has an RS485 connection for a serial repeater. The repeaters has full control. Up to 3 repeater
can be powered from the Aux 24V DC output on the panel. If 4 or more are to be connected, then they must be
powered from external 24V power supplies. The panel supports up to 8 repeaters.
ID2 PANEL ID2 REPEATER
ID2 Panel
ID2 Repeater
Description
AUX 28V +
24V DC IN +
Power for repeater
AUX 28V 1
24V DC IN -
Power for repeater
RS485 B
RS485 B
Data connection
RS485 A
RS485 A
Data connection
RS485 GND
RS485 GND
Data connection screen
Vista de página 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 35 36

Comentários a estes Manuais

Sem comentários